Data Sheet for Product

16 / 22
A6V10421228_en--_c Climatix controller POL424.70/STD Siemens
2021-09-10 Smart Infrastructure
Mode
LED status
SW update mode (download active
on a new BSP, application)
Alternating between red and green every
second
Application running Green on
Application loaded but not running Orange on
Application not loaded Orange on
BSP error (software error) Red flashing at 2 Hz
Hardware error Red on
LED for bus is not in operation.
Possible plugs for I/O signals and
communication (available on
request)
Phoenix FKCVW 2,5/x-ST
Phoenix FKCT 2,5/x-ST
Phoenix MVSTBW 2,5/x-ST
Possible plugs for power supply
(available on request)
Phoenix FKCVW 2,5/2-ST OG
Phoenix FKCT 2,5/2-ST OG
Phoenix MVSTBW 2,5/2-ST OG
Solid wire 0.5…2.5 mm²
Stranded wire (twisted or with
ferrule)
0.5…1.5 mm²
Buffering with internal Gold Cap Min. 4 hours
SD card At the right side of the housing
Max. capability 32 GB
Format FAT32
Note: New SD card must be formatted
with FAT32 standard before use.
Operation
IEC 60721-3-3
Temperature -20…60 °C
Humidity < 90% r.h. (non-condensing)
Air pressure Min. 700 hPa, corresponding to
Max. 3,000 m above sea level
Transport
IEC 60721-3-2
Temperature -40...70 °C
Humidity < 95% r.h. (non-condensing)
Air pressure Min. 260 hPa, corresponding to
Max. 10,000 m above sea level
Mechanical conditions IEC 60721-3-2 Class 2M2
Degree of protection IP20 (EN 60529)
Safety class Suitable for use in plants with safety
class II
LED
for BSP run
/
stop
Note:
Connection terminals
Real
-
time clock
SD card
Environment
Protection