Data Sheet for Product
13 / 22
Siemens Climatix controller POL424.70/STD A6V10421228_en--_c
Smart Infrastructure 2021-09-10
0/1 digital signal (binary) For potential-free contacts
Sampling voltage / current DC 24 V, 8 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay 10 ms
Pulse frequency Max. 20 Hz
Configurable By software
0/1 digital signal
(binary)
For potential-free contacts
Sampling voltage / current DC 24 V, 8 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay 10 ms
Pulse frequency Max. 20 Hz
Pulse
m
easurement
Sensor Open-collector
Sampling voltage DC 24 V, Max. 8 mA
Max. speed 6000 RPM
Min. ON / OFF time 500 µs
Voltage / current DC 5 V ±2.5%, 20 mA
Voltage / current DC 24 V (-25%, +10%), 40 mA
Reference potential Terminals ┴
Connection Short-circuit protected
Digital inputs
X6, X7 (T3)
DI1, DI2 (T4)
Digital input
X8 (T3)
Powering supply for
sensors
Active / ratiometric
DC 5 V, DC 24 V (T2)