Data Sheet for Product
11 / 22
Siemens Climatix controller POL424.70/STD A6V10421228_en--_c
Smart Infrastructure 2021-09-10
LG
-
Ni1000 (TK5000
)
/
Pt1000
Sensor current 1.4 mA at 0 °C
Temperature range -48…150 °C
Accuracy ±1 K
Resolution ±0.25 K
These data are acquired under operating temperature of 25 °C.
Configurable By software
Reference potential Terminals ┴
LG
-
Ni1000 (TK5000
)
Accuracy Please refer to B1…B3
DC
0
…
5
/
0
…
10
V
r
atiometric
s
ensor
Resolution 50 mV
Accuracy 100 mV
Input resistance 100 kΩ
Digital
i
nput
0/1 digital signal (binary) For potential-free contacts
Sampling voltage / current DC 24 V, 8 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay 10 ms
Pulse frequency Max. 20 Hz
Configurable inputs
X1, X2 (T2)