Data Sheet for Product
10 / 22
A6V10421228_en--_c Climatix controller POL424.70/STD Siemens
2021-09-10 Smart Infrastructure
Relay
Contact Monostable, NO contact, SPST
Switching voltage AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res. / ind.) AC 3 A (res.) / 2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current at AC 19 V 30 mA
Endurance 100,000 cycles at AC 230 V, 3.0 A (res.)
Max. external supply line fusing 6.3 A slow wire fuse or circuit breaker
Do not mix SELV /
PELV and line voltage
on the same terminal.
Use external protection
for inductive load.
Relay
Contact Monostable, NO contact, SPST
Switching voltage AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res. / ind.) AC 3 A (res.) / 2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current at AC 19 V 30 mA
Endurance 100,000 cycles at AC 230 V, 3.0 A (res.)
Max. external supply line fusing 6.3 A slow wire fuse or circuit breaker
Do not mix SELV / PELV
and line voltage on the
same terminal.
Use external protection
for inductive load.
Relay outputs
Q3, Q4 (T9)
Q5, Q6 (T10)
Relay outputs
Q7, Q8 (T11)