Data Sheet for Product
6
Siemens
CB1Q3973_en--_e
Smart Infrastructure
2022-03-21
WARNING
Do NOT mix SELV / PELV and line voltage on the same terminal.
Use external protection for inductive load.
Relay output
Q3, Q4 (T9)
Q5, Q6 (T10)
Contact
Monostable, NO contact, SPST
Switching voltage
AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res./ind.)
AC 3 A (res.)/2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current @ AC 19 V
30 mA
Endurance
100,000 cycles @ AC 230 V, 3.0 A (res.)
Max. external supply line fusing
6.3 A slow wire fuse or circuit breaker