Communication concept
Type summary
Type
Photo
POL424.50/XXX
Notes
Engineering
In order to protect against accidental contact with relay connections at voltages above 42
Veff, the device must be installed in an enclosure (preferably a control panel). It must be
impossible to open the enclosure without the aid of a key or tool.
AC 115…230 V cables must be double-insulated against safety extra-low voltage (SELV)
cables.
Do NOT mix SELV / PELV and line voltage on the same terminal.
Use external protection for inductive load of relay outputs.
Use external fuse for over current protection of relay outputs.
Avoid negative voltage on analogue inputs, because the measured ADC values are
undefined. The accuracy of the 10 V analogue inputs is valid for values above 100 mV.