Data Sheet for Product

Climatix™
Climatix programmable controllers
POL424.50/XXX
The Climatix POL424.50/XXX programmable controllers are HVAC controllers
optimized for air handling units, rooftop units, chillers and heat pumps.
Power supply AC 24 V or DC 24 V
DC 24 V and DC 5 V power supplies for active sensors on board
3 analog inputs for temperature sensor
2 configurable inputs as digital input/DC 0…10 V input/temperature sensor
3 configurable outputs as DC 0…10 V analog output/digital output for off-board
load
4 digital inputs for potential-free contacts
1 digital input for potential-free contact or fan speed measurement
1 digital input galvanically isolated (AC 115…230 V)
7 relay outputs (6 NO contacts, 1 changeover switching type)
RS-485 for Modbus RTU or BACnet MS/TP (with VVS10.50 or higher) for third-
party bus communication
Process bus for network functionalities
Local service connector for user interface and PC tools (supporting USB)
SD card interface for application and operating system upgrade
Operating temperature range is -40…70 °C
Powerful service tools are available to facilitate commissioning.
CB1Q3973_en--_e
2022-03-21