User Manual

Climatix POL42X.70 variants list
Hardware I/Os
POL421.70/STD
POL422.70/STD
POL424.70/STD
Analog
inputs
B1, B2, B3 (NTC 10k)
B1, B2, B3 (LG-Ni1000 / Pt1000)
Configurable
inputs
X1, X2 (NTC 10k / DC 0…10 V / DI)
X1, X2 (LG-Ni1000 / DC 0…10 V / DI)
Digital inputs
X6, X7 (binary)
X8 (binary / fan speed)
D1, D2 (binary)
DL1 (active AC 115…230 V)
Configurable
outputs
X3, X4, X5 (DC 0...10 V analog output /
offboard digital output)
Digital outputs
Q1, Q3, Q4, Q5, Q6 (relay output)
Q7, Q8 (relay output)
DO1, DO2 (triac output)
Interfaces
Process bus interface
Modbus RTU or BACnet MSTP interface
EEV (stepper motor drive / PWM)
SD card interface
Mounting instructions
- The product is used for flush panel mounting with a front mounting kit.
- Do not mount the product in recesses, shelving, behind curtains or doors or
above or near direct heat sources.
- Avoid exposure to direct sunlight and draught.
- Seal the conduit on the device side, as currents of air in the conduit can affect
the sensor reading.
- Observe the admissible ambient conditions.
Ordering
Please specify the quantity, product name, ASN and SSN when ordering. The
following information is an example:
Minimum
Order
Quantity
Product name ASN (product no.) SSN (stock no.)
18
Climatix 400 controller with Inbuilt
HMI
POL421.70/STD S55394-C217-A100
18
Climatix 400 controller with Inbuilt
HMI
POL422.70/STD S55394-C227-A100
18
Climatix 400 controller with Inbuilt
HMI
POL424.70/STD S55394-C247-A100
21 / 24
Siemens Climatix controllers POL42X.70/STD A6V10421228_en--_b
Building Technologies 2016-04-07