User Manual
Climatix POL42X.70 variants list
Hardware I/Os
POL421.70/STD
POL422.70/STD
POL424.70/STD
Analog
inputs
B1, B2, B3 (NTC 10k)
√
√
B1, B2, B3 (LG-Ni1000 / Pt1000)
√
Configurable
inputs
X1, X2 (NTC 10k / DC 0…10 V / DI)
√
√
X1, X2 (LG-Ni1000 / DC 0…10 V / DI)
√
Digital inputs
X6, X7 (binary)
√
√ √
X8 (binary / fan speed)
√
√ √
D1, D2 (binary)
√
√ √
DL1 (active AC 115…230 V)
√
√ √
Configurable
outputs
X3, X4, X5 (DC 0...10 V analog output /
offboard digital output)
√ √ √
Digital outputs
Q1, Q3, Q4, Q5, Q6 (relay output)
√ √ √
Q7, Q8 (relay output)
√ √
DO1, DO2 (triac output)
√
Interfaces
Process bus interface
√ √
Modbus RTU or BACnet MSTP interface
√ √ √
EEV (stepper motor drive / PWM)
√ √
SD card interface
√
√
√
Mounting instructions
- The product is used for flush panel mounting with a front mounting kit.
- Do not mount the product in recesses, shelving, behind curtains or doors or
above or near direct heat sources.
- Avoid exposure to direct sunlight and draught.
- Seal the conduit on the device side, as currents of air in the conduit can affect
the sensor reading.
- Observe the admissible ambient conditions.
Ordering
Please specify the quantity, product name, ASN and SSN when ordering. The
following information is an example:
Minimum
Order
Quantity
Product name ASN (product no.) SSN (stock no.)
18
Climatix 400 controller with Inbuilt
HMI
POL421.70/STD S55394-C217-A100
18
Climatix 400 controller with Inbuilt
HMI
POL422.70/STD S55394-C227-A100
18
Climatix 400 controller with Inbuilt
HMI
POL424.70/STD S55394-C247-A100
21 / 24
Siemens Climatix controllers POL42X.70/STD A6V10421228_en--_b
Building Technologies 2016-04-07