User Manual
Mode
LED status
SW update mode (download active
on a new BSP, application)
Alternating between red and green every
second
Application running
Green on
Application loaded but not running
Yellow on
Application not loaded
Yellow on
BSP error (software error)
Red flashing at 2 Hz
Hardware error
Red on
LED for bus is not in operation.
Possible plugs for I/O signals and
communication (available on request)
Phoenix FKCVW 2,5/x-ST
Phoenix FKCT 2,5/x-ST
Phoenix MVSTBW 2,5/x-ST
Possible plugs for power supply
(available on request)
Phoenix FKCVW 2,5/2-ST OG
Phoenix FKCT 2,5/2-ST OG
Phoenix MVSTBW 2,5/2-ST OG
Solid wire
0.5…2.5 mm²
Stranded wire (twisted or with ferrule)
0.5…1.5 mm²
Buffering with internal Gold Cap
Min. 4 hours
SD card
At the right side of the housing
Max. capability
32 GB
Format FAT32
Note: New SD card must be formatted with
FAT32 standard before use.
Operation
IEC 60721-3-3
Temperature
-20…60 °C
Humidity
< 90% r.h. (non-condensing)
Air pressure Min. 700 hPa, corresponding to
Max. 3,000 m above sea level
Transport
IEC 60721-3-2
Temperature
-40...70 °C
Humidity
< 95% r.h. (non-condensing)
Air pressure Min. 260 hPa, corresponding to
Max. 10,000 m above sea level
Mechanical conditions
IEC 60721-3-2 Class 2M2
Degree of protection
IP20 (EN 60529)
Safety class
Suitable for use in plants with safety
class II
LED for BSP run / stop
Note:
Connection terminals
Real-time clock
SD card
Environment
Protection
19 / 24
Siemens Climatix controllers POL42X.70/STD A6V10421228_en--_b
Building Technologies 2016-04-07