User Manual

0/1 digital signal (binary)
For potential-free contacts
Sampling voltage / current
DC 24 V, 8 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay
10 ms
Pulse frequency
Max. 20 Hz
Configurable
By software
0/1 digital signal (binary)
For potential-free contacts
Sampling voltage / current
DC 24 V, 8 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay
10 ms
Pulse frequency
Max. 20 Hz
Pulse measurement
Sensor
Open-collector
Sampling voltage
DC 24 V, Max. 8 mA
Max. speed
6000 RPM
Min. ON / OFF time
500 µs
Voltage / current
DC 5 V ±2.5%, 20 mA
Voltage / current
DC 24 V (-25%, +10%), 40 mA
Reference potential
Terminals
Connection
Short-circuit protected
Digital input
s
X
6, X7 (T3)
DI1, DI2 (T4)
Digital input
X8 (T3)
Powering supply for
sensors
Active / ratiometric
DC 5 V, DC 24 V (T2)
16 / 24
A6V10421228_en--_b Climatix controllers POL42X.70/STD Siemens
2016-04-07 Building Technologies