User Manual
LG-Ni1000 (TK5000) / Pt1000
(Assembled in POL424.70)
Sensor current
1.4 mA at 0 °C
Temperature range
-48…150 °C
Accuracy
±1 K
Resolution
±0.25 K
0.40
0.60
0.80
1.00
1.20
-48.0 -25.0 0.0 25.0 100.0 125
.
0 150.0
Temperature [°C]
Accuracy [K]
0.00
0.20
50.0 75.0
0.
1000
0.
1500
0
.2000
0.
2500
0
.
3000
-
48
.0
-
25.
0 0
.
0 2
5.
0
100.
0 125
.
0 150
.
0
Temperature [
°C
]
Resolution [
K]
0
.0000
0.
5000
50
.0
7
5.
0
These data are acquired under operating temperature of 25 °C.
Configurable
By software
Reference potential
Terminals ┴
NTC 10k (B
25/85
=3977 K)
(Assembled in POL421.70, POL422.70)
Accuracy
Please refer to B1…B3
LG-Ni1000 (TK5000)
(Assembled in POL424.70)
Accuracy
Please refer to B1…B3
DC 0…5 / 0…10 V ratiometric sensor
Resolution
50 mV
Accuracy
100 mV
Input resistance
100 kΩ
Digital input
0/1 digital signal (binary)
For potential-free contacts
Sampling voltage / current
DC 24 V, 8 mA
Contact resistance
Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay
10 ms
Pulse frequency
Max. 20 Hz
Configurable inputs
X1, X2 (T2)
14 / 24
A6V10421228_en--_b Climatix controllers POL42X.70/STD Siemens
2016-04-07 Building Technologies