User Manual

Relay
Contact
Monostable, NO contact, SPST
Switching voltage AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res. / ind.)
AC 3 A (res.) / 2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current at AC 19 V
30 mA
Endurance
100,000 cycles at AC 230 V, 3.0 A (res.)
Max. external supply line fusing
6.3 A slow wire fuse or circuit breaker
Do not mix SELV / PELV
and line voltage on the
same terminal.
Use external protection
for inductive load.
Relay
(Assembled in POL421.70, POL424.70)
Contact
Monostable, NO / NC contact, SPST
Switching voltage
AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res. / ind.)
AC 3 A (res.) / 2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current at AC 19 V
30 mA
Endurance
100,000 cycles at AC 230 V, 3.0 A (res.)
Max. external supply line fusing
6.3 A slow wire fuse or circuit breaker
Do not mix SELV / PELV
and line voltage on the
same terminal.
Use external protection
for inductive load.
Relay outputs
Q3, Q4 (T9)
Q5, Q6 (T10)
Relay outputs
Q7, Q8 (T11)
12 / 24
A6V10421228_en--_b Climatix controllers POL42X.70/STD Siemens
2016-04-07 Building Technologies