s Climatix TM Climatix controllers POL42X.70/STD For controlling, switching and monitoring functions The Climatix 42X.70/STD controllers are optimized with Inbuilt HMI for air handling units, rooftop units, chillers and heat pumps, available for display, unit configuration and operation. Controller types POL421.70/STD POL422.70/STD POL424.
Main features The Climatix 42X.
Overview (POL 421.70/STD) Power supply Analog inputs Configurable inputs Sensor power supply Digital outputs Configurable outputs Digital inputs Active digital input EEV RS485 Service interface 3 / 24 Siemens Building Technologies Climatix controllers POL42X.
Overview (POL 422.70/STD) Power supply Analog inputs Configurable inputs Sensor power supply Digital outputs Configurable outputs Digital inputs Active digital input EEV RS485 Service interface Process bus 4 / 24 A6V10421228_en--_b 2016-04-07 Climatix controllers POL42X.
Overview (POL 424.70/STD) Power supply Analog inputs Configurable inputs Sensor power supply Digital outputs Configurable outputs Digital inputs Active digital input RS485 Service interface Process bus 5 / 24 Siemens Building Technologies Climatix controllers POL42X.
Application LCD Display The FSTN LCD display is subdivided into several logical blocks, containing symbols and characters associated with specific operating states to provide real time information. All icons can be programmed with the following status via SCOPE and SAPRO (regardless of whether the application controls the Inbuilt HMI): - Fixed display Flashing (interval: 500 ms) Non display 1 A6V10421226J02 5 ° . . . . . 2 Segment introduction °C °F Psi bar % KPa 6 1 2 3 4 5 3 6 7 4 No.
Icon introduction Icon Explanation Icon Engeneering unit segment Explanation Device segment °C Degrees Celsius Supply °F Degrees Fahrenheit Exhaust K Kelvin Fan Psi, bar Pressure in Psi or bar Pump Pa Pressure in Pascal Compressor KPa Presure in kPascal Radiator Menu segment Domestic hot water Data Solar Plant information Damper Alarm Valve Maintenance Capacity Time setting Heating coil Loop setting Cooling coil Stage setting Electric-heating coil Defrost Heat recov
The special symbols are displayed on the first line as follows: Special symbols on the first line + Numeral represented Latin letters - * . _ \ / The Latin letters are displayed on the first line as follows: Uppercase letter on Uppercase letter Lowercase letter on Lowercase letter the first line represented the first line represented A B a b C c D d E e F G H I f g h i J K L M N O P Q R j k l m n o p q r S s T U V W X Y Z t u v w x y z 8 / 24 A6V10421228_en--_b 2016-04-07
Cyrillic letters The Cyrillic letters are displayed on the first line as follows: Cyrillic letter on the first line Uppercase letter represented Lowercase letter represented А Б а б B в Г г Д E Ё Ж д e ё ж З И Й К Л M H O П P C T У Ф X Ц Ч Ш Щ Ъ з и й к л м н о п р с т у ф х ц ч ш щ ъ Ы Ь Ю Я ы ь ю я Э э 9 / 24 Siemens Building Technologies Climatix controllers POL42X.
Operating mode The following running modes are customized as operating modes for easy of selection. Operating mode Value Comfort Heat 1 Comfort Cool 2 PreComfort Heat 3 PreComfort Cool 4 Economy Heat 5 Economy Cool 6 Heat Pump 7 Economy Heat Pump 8 AUTO 1) Standby 1) 15 Combination icons AUTO 0 Other combination icons can be displayed together with AUTO according to the real running mode. 10 / 24 A6V10421228_en--_b 2016-04-07 Climatix controllers POL42X.
Disposal The devices are considered electronics devices for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic waste. • Dispose of the device via the channels provided for this purpose. • Comply with all local and currently applicable laws and regulations. Technical data Power supply AC 24 V, G0 (T7) Operating voltage Frequency Max. AC current Max. DC current Max.
Relay outputs Q3, Q4 (T9) Q5, Q6 (T10) Relay Contact Switching voltage Rated current (res. / ind.) Min. switching current at AC 19 V Endurance Max. external supply line fusing Monostable, NO contact, SPST AC 24…230 V (-20%, +10%) DC 18…30 V AC 3 A (res.) / 2 A (ind. cosφ 0.6) DC 3 A (res.) 30 mA 100,000 cycles at AC 230 V, 3.0 A (res.) 6.3 A slow wire fuse or circuit breaker Do not mix SELV / PELV and line voltage on the same terminal. Use external protection for inductive load.
Triac outputs DO1, DO2 (T11) Triac data Switching voltage Switching capacity (Assembled in POL422.70) AC 24…230 V (-20%, +10%) Max. 500 mA 1) Min. 30 mA Max. external supply line fusing 2.0 A slow wire fuse or circuit breaker 1) The minimum value depends on environment temperature. Do not mix SELV / PELV and line voltage on the same terminal. Use external protection for inductive load.
(Assembled in POL424.70) 1.4 mA at 0 °C -48…150 °C ±1 K ±0.25 K 1.20 0.3000 1.00 0.2500 0.80 0.2000 Resolution [K] Accuracy [K] LG-Ni1000 (TK5000) / Pt1000 Sensor current Temperature range Accuracy Resolution 0.60 0.1500 0.40 0.1000 0.20 0.5000 0.00 -48.0 -25.0 0.0 25.0 50.0 75.0 100.0 125.0 150.0 0.0000 -48.0 -25.0 Temperature [°C] 0.0 25.0 50.0 75.0 100.0 125.0 150.0 Temperature [°C] These data are acquired under operating temperature of 25 °C.
Avoid negative voltages at the analog inputs because the conversion leads to indetermined results. Configurable outputs X3, X4 (T2), X5 (T3) Note: Configurable Reference potential By software Terminals ┴ DC 0…10 V output Resolution Accuracy Output current 30 mV 100 mV Max. 1 mA DC output for off-board load Switching voltage Switching capacity DC 24 V Max. 25 mA Use free wheel diode for inductive load. 15 / 24 Siemens Building Technologies Climatix controllers POL42X.
Digital inputs X6, X7 (T3) DI1, DI2 (T4) Digital input X8 (T3) 0/1 digital signal (binary) Sampling voltage / current Contact resistance Delay Pulse frequency For potential-free contacts DC 24 V, 8 mA Max. 200 Ω (closed) Min. 50 kΩ (open) 10 ms Max. 20 Hz Configurable By software 0/1 digital signal (binary) Sampling voltage / current Contact resistance For potential-free contacts DC 24 V, 8 mA Max. 200 Ω (closed) Min. 50 kΩ (open) 10 ms Max.
Active digital input DL1 (T12) Digital input (0/1 binary) Nominal voltage Frequency range Input current Delay Pulse frequency Galvanic isolated voltage input AC 115…230 V (-15%, +10%) 45…65 Hz 3 mA at AC 230 V 100 ms Max. 5 Hz EEV (T13) Configurable Connector By software B6B-XH-A, JST Stepper motor drive Motor (Assembled in POL421.70, POL422.70) Unipolar stepper motor DC 12 V, Max.
Interfaces Process bus CE+, CE- (T6) Based on KNX TP1 Bus connection Bus electronics Bus load Bus cable Bus cable length between 2 nodes Total length of bus cable DPSU Third-party bus (RS-485 Modbus RTU or BACnet MSTP) A+, B-, REF (T5) Note: Tools / HMI Local service interface (T-HI) (Assembled in POL422.70, POL424.70) CE+, CE-, not interchangeable Galvanic isolated Max. 5 mA Must be shielded; Please refer to KNX manual - System Specifications Max. 350 m Max.
LED for BSP run / stop Mode SW update mode (download active on a new BSP, application) Application running Application loaded but not running Application not loaded BSP error (software error) Hardware error Note: LED for bus is not in operation.
Standards EU Conformity (CE) Listings RCM conformity 800080034_xx *) UL916, UL873 CSA C22.2M205 8000080035 *) Environmental compatibility The product environmental declaration A5Q00058873H-01-78 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). General data Dimensions Weight excl.
POL422.70/STD B1, B2, B3 (NTC 10k) √ √ B1, B2, B3 (LG-Ni1000 / Pt1000) X1, X2 (NTC 10k / DC 0…10 V / DI) √ √ Hardware I/Os Analog inputs Configurable inputs POL424.70/STD POL421.70/STD Climatix POL42X.70 variants list √ X1, X2 (LG-Ni1000 / DC 0…10 V / DI) X6, X7 (binary) √ √ √ √ X8 (binary / fan speed) D1, D2 (binary) √ √ √ √ √ √ DL1 (active AC 115…230 V) X3, X4, X5 (DC 0...
Engineering notes In order to protect against accidental contact with relay connections at voltages above 42 Veff, the device must be installed in an enclosure (preferably a control panel). It must be impossible to open the enclosure without the aid of a key or tool. AC 230 V cables must be double-insulated against safety extra-low voltage (SELV) cables. Do not mix SELV / PELV and line voltage on the same terminal. Use external protection for inductive load of relay outputs.
Dimensions (mm) POL 421.70/STD POL 422.70/STD POL 424.70/STD 23 / 24 Siemens Building Technologies Climatix controllers POL42X.
/ 24 © Siemens Switzerland Ltd, 2015 - 2016 A6V10421228_en--_b 2016-04-07 Climatix controllers POL42X.