Data Sheet for Product

2 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Installation concept
Disposal
The devices are considered electronics devices for disposal in term of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
· Dispose of the device via the channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.
Technical data
Operating voltage AC 24 V ±20%; DC 24 V ±10%
Frequency 45…65 Hz
Max. AC-Current consumption 600 mA at AC 24 V
Max. DC-Current consumption 340 mA at DC 24 V
Connection Peripheral bus
Max. pass through current 3.4 A at AC 24V
3.66 A at DC 24 V
Relay: type, contact Monostable, NO contact
Contact rating
Switching voltage AC 24…230 V (-20%, +10%)
Nominal current (res. / ind.) Max. AC 4 A / 3 A (cosφ 0.6)
Switching current at AC 19 V Min. AC 30 mA
Connecting indicator lamps to relay output
Climatix
p
roduct
r
ange
Power supply
Power
Relay outputs
Q1..
.
Q4