User Manual

8 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
DIP Switch configuration of Extension Module
No. Schematics No. Schematics No. Switch 5 No. Schematics
7 15 23 31
8 16 24
The same address of extension module must be set respectively in the application
program of the controller. 0 cannot be set as the slave address.
Climatix I/O extension module 14 I/Os 1 pcs POL955.00/STD
Connector set (spring cage, cable top entry) or 1 pcs POL095.56/STD
Connector set (screw, cable side entry) 1 pcs POL095.55/STD
Connector set (spring cage, cable top entry) POL095.56/STD
1 x Phoenix FKCT 2,5/2-ST GY7035
1 x Phoenix FKCT 2,5/3-ST GY7035
3 x Phoenix FKCT 2,5/6-ST GY7035
1 x Phoenix ZEC 1,0 / 4-LPV-3,5 GY35AUC2CI1
Connector set (screw, cable side entry) POL095.55/STD
1 x Phoenix MVSTBW 2,5/2-ST GY7035
1 x Phoenix MVSTBW 2,5/3-ST GY7035
3 x Phoenix MVSTBW 2,5/6-ST GY7035
1 x Phoenix ZEC 1,0 / 4-LPV-3,5 GY35AUC2CI1
Board-to-wire connector POL002.43/STD
2 x Phoenix ZEC 1,0 / 4-ST-3,5 GY35AUC1R1,4 50 pcs
Engineering notes
To ensure protection against accidental contact with relay connections carrying
voltages above 42 V
eff
, the extension module must be installed in an enclosure
(preferably a control panel). It must be impossible to open the enclosure without
the aid of a key or tool.
AC 230 V cables must be double-insulated against safety extra low-voltage (SELV)
cables.
Note
F
Ordering
data
Accessories