User Manual
2 / 6
Siemens Climatix extension module 6 I/Os CB1N3924en_04
Smart Infrastructure 2020-09-23
Installation concept
Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the devices through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Operating voltage
AC 24 V ± 20%; DC 24 V ± 10%
Frequency
45…65 Hz
Max. AC-Current consumption
0.15 A
Max. DC-Current consumption
0.065 A
Connection
Peripheral bus
Max. pass through current
3.85 A at AC 24 V
3.935 A at DC 24 V
0/1 digital signal(binary)
For potential-free contacts
Sampling voltage / current
DC 24 V / 8 mA
Contact resistance
Max.200 Ω (closed)
Min. 50 kΩ (open)
Delay
10 ms
Pulse frequency
Max. 30 Hz
Connecting floating contacts
Climatix product range
Power supply
Power distribution
Digital inputs
D1...D4 (T1)