User Manual

Technical data
If not mentioned otherwise, the following data apply to all computer types.
Power supply
Mains voltage
PLD7.tower and rack
230 V / 110 V
(200 – 240 / 100 – 127)
Fusing
PLD7.tower and rack
10 A
Mains frequency:
50/60 Hz
Power consumption:
PLD7.tower and rack
3.5 A / 7 A++
max. 275 W
Dimensions
H x W x D in cm, no plug
PLD7.tower
PLD7.rack
PLD7.rack (installation depth)
444 x 205 x 605
5 units (U)
560 (no plug)
Weight
PLD7.tower and rack
1 hot plug disk
21 kg
710 Gr.
Ambient conditions
Operating temperature: 10 ... 35 °C (as per IEC 721)
Relative humidity: 15...80% (non-condensing)
Change of humidity:
< 5% r. h. per hour
BLN data transmission
System bus protocol: SDLC/FSK
Data transmission V.24
Transmission speeds for terminals,
INSIGHTs, printers, modems
as specified
Network data transmission
Transfer protocol
Networks
Transmission speed
Chip
TCP/IP, NetBIOS on TCP/IP
Ethernet
10/100 Mbps
INTEL 82559
Conformity
EMC directive
Low voltage directive:
89/ 336/EEC
73/23/EEC (Product safety)
Electromagnetic
compatibility
Emissions:
Immunity:
EN 55 022 class A; EN 55 024
EN 61000-3-2 and EN 61000-3-3
Product standards
Safety of information technology
equipment
IEC 950 / EN 60950
UL 1950, CSA 22,2 No. 950
.
.
2000 Siemens Building Technologies AG Subject to chang
e
6/6
Siemens Building Technologies DCS Data and Communication Server CM2N8559en
Building Automation 21.10.2002