Specifications
Industrial PC
DC UPS uninterruptible power supplies
Introduction
3/83
Siemens ST PC · November 2008
3
■
Overview
By combining a SITOP power supply unit with a DC UPS module
and with at least one 24 V battery module or a maintenance-free
SITOP UPS500S (optionally with extension module), longer
power failures can be bridged without any interruption.
This combination is used, for example, in machine tool manufac-
ture, the textile industry, all types of production lines and filling
systems, and in conjunction with 24 V industrial PCs. This pre-
vents the negative effects which often result from power failures.
For SIMATIC PC this implies a failsafe shut down of all current
applications, as well of the operating system.
For “NON-STOP” use in the event of power failures, Siemens
offers the following uninterruptible power supplies:
• DC UPS 6 A
• DC UPS 15 A
• DC UPS 40 A
and the following battery modules:
• 1.2 Ah (contains lead-acid batteries with corrosion-resistant
lead-calcium, high-capacity grid plates and fiberglass mat)
• 3.2 Ah (contains lead-acid batteries with corrosion-resistant
lead-calcium, high-capacity grid plates and fiberglass mat)
• 7 Ah (contains lead-acid batteries with corrosion-resistant
lead-calcium, high-capacity grid plates and fiberglass mat)
• 12 Ah (contains lead-acid batteries with corrosion-resistant
lead-calcium, high-capacity grid plates and fiberglass mat)
• 2.5 Ah (contains “high-temperature battery” lead-acid type)
The maintanance-free DC UPS modules with capacitors as
energy storage are particularly suitable for operation in high
ambient tamperatures:
• SITOP UPS500S (DC UPS basic unit 15 A 2.5 kWs)
• SITOP UPS500S (DC UPS basic unit 15 A 5 kWs)
Optionally for increasing the buffer time:
• SITOP UPS501S (capacitor module 5 kWs)
■
Ordering data Order No. Order No.
G_KT01_EN_00357
24 V DC 24 V DC
Messages
- Mains or buffer operation
- Buffer ready or alarm
Charging status >85 % or <85 %
via USB interface or floating relay contacts
USB interface for data exchange with
industrial PC
SITOP UPS500S basic unit 15 A
with capacitor module as additional energy storage
AC or 3 AC
Examples for SITOP power supplies:
SITOP modular 5 A
6EP1 333-3BA00
Input 120/230 – 500 V AC
Output 24 V / 5 A DC
SITOP modular 10 A
6EP1 334-3BA00
Input 120/230 – 500 V AC
Output 24 V / 10 A DC
Examples for SITOP power supplies:
SITOP smart 5 A
6EP1 333-2BA01
Input 120/230 V AC
Output 24 V / 5 A DC
SITOP smart 10 A
6EP1 334-2BA01
Input 120/230 V AC
Output 24 V / 10 A DC
© Siemens AG 2009