Specifications
Industrial PC
SIMATIC Panel PC
Introduction
3/36
Siemens ST PC · November 2008
3
■
Overview (continued)
SIMATIC Panel PC 477B
embedded
SIMATIC Panel PC 577B SIMATIC Panel PC 677B
Design
Centralized configuration
• • •
Distributed configuration
(via remote kit)
– –
I
2)
Display
Size 12"/15"/19“ TFT 12"/15"/19“ TFT 12”/15”/15” INOX/17”/19” TFT
Resolution 800 x 600 / 1 024 x 768 /
1 280 x 1 024
800 x 600 / 1 024 x 768 /
1 280 x 1 024
800 x 600 / 1 024 x 768 /
1 280 x 1 024
Operator controls
Membrane keyboard I
1)
–
I
1)
Touch screen
• • •
General features
Power supply
24 V DC / 110/230 V AC
I / – – / I I / I
Processor Intel Celeron M 1.0 GHz;
Intel Pentium M 1.4 GHz
Intel Celeron M 1.86 GHz Intel Celeron M 1.86 GHz;
Intel Core 2 Duo 1.66 GHz;
Intel Core 2 Duo 2.16 GHz
Main memory 1 GB or 2 GB 1 GB, expandable to 4 GB 1 GB; 2 GB;
3 GB; 4 GB
Expansion slots 3 x PC/104
2)
; 2 x CF-Slot
(1 x accessible from outside)
2 x PCI
3)
; 1 x CF slot
(accessible from outside)
2 x PCI or 1 x PCI and
1 x PCIe x4
3)
; 1 x CF slot
Operating system Windows XP embedded
on CF Card
None;
Windows XP Professional MUI
None;
Windows 2000 Professional MUI;
Windows XP Professional MUI;
Windows Vista Ultimate MUI;
Windows XP embedded on CF
Interfaces
PROFIBUS / MPI
•
–
4)
•
PROFINET
•
–
4)
•
Ethernet 10/100/1 000 MBit 10/100/1 000 MBit 10/100/1 000 MBit
PS/2 (mouse/keyboard)
– – –
USB
• • •
Serial interface
• • •
Parallel interface
– – –
Audio in/out
– – –
Graphics interface
• • •
Ambient conditions
Vibration load during operation 1 g 0.25 g 1 g
Shock loading during operation 5 g 1 g 5 g
Permissible temperature during ope-
ration with maximum configuration
+5 … +50 °C +5 … +45 °C
8)
+5 … +50 °C
5)
Power loss in maximum
configuration
12“/15“ display 80 W
6)
140 W
7)
140 W
7)
17“/19“ display 110 W
6)
163 W
7)
163 W
7)
Available
Not available
1)
12“/15“ displays
2)
With optional expansion rack
3)
All slots with card retainer
4)
Expandable via plug-in card
5)
With 17"/19" Touch: +5 ... 45 °C; max. 50 °C in installation space, if at the front max. 40 °C
6)
3 W taken into account for each PC/104 slot
7)
15 W taken into account for each PCI/PCIe slot
8)
max. 50 °C in installation space, if at the front max. 40 °C
•
–
© Siemens AG 2009