Operating instructions

Application planning
4.4 Mounting positions and fastening
SIMATIC Panel PC 677B
Operating Instructions, 05/2007, A5E01035609-01
29
4.4.4 Protection against dust and water
Principle
With the relevant installation, the device is protected on the front agains the ingress of dust
and water. The "degree of protection" is in accordance with IEC 60529: On the front, the
device has degree of protection IP65, the rear of the operator section and the computer unit
have degree of protection IP20.
Caution
Ensure that the material strength at the mounting cut-out is a minimum of 2 mm and a
maximum of 6 mm. Please follow the specifications for the dimensions in the "Mounting cut-
out" section.
The degrees of protection IP65, IP54 and NEMA 4, are only guaranteed when the following
conditions are met:
The surface plane deviation of the mounting cut-out in relation to the external
dimensions of the control unit amounts to ≤ 0.5 mm when the control unit is mounted.
Degree of protection IP65 and NEMA 4
IP65 degree of protection and compliance with the NEMA 4 regulations are only ensured
when clamp mounting together with a ring seal.
IP54 degree of protection
The IP54 degree of protection is applicable for the following conditions:
Key panel Touch panel
12" 15" 15" 17" 19"
Screw mounting X X X - -
Screw mounting with backing
plate
- - - X X
Note
A backing plate is available as an accessory for screw mounting the 17" and 19" touch
panel. You can find additional information under:
http://www.siemens.com/automation/mall