Technical data

Release 03/03 Supplement to Panel PC 670 and 870 Start-up Guide
Supplement to Start-up Guide
A5E00212362
23/30
Windows NT4 with SP6
Restore CD 1, Windows NT, German A5E00161375
Restore CD 1, Windows NT, English A5E00161369
can only be used for Panel PC 870s with order numbers 6AV770x-xCxx-... and
6AV771x-xDxx-... (image of hard disk C: which is transferred back using Easy
Restore and restores the initial state of the unit).
Notice
Images from other Panel PCs (e.g. order numbers 6AV76... and 6AV77...)
cannot be restored on the Panel PC 870 with order numbers 6AV770... or
6AV771... due to the implementation of different chipsets and drivers.
1.8 Power Supply
Warning
Panel PCs with a DC power supply may only be connected to a 24 V power
supply network which complies with the requirements of safety extra low
voltage (SELV).
The cross-section of the cable must be sufficiently large so that in the case of a
short circuit on the Panel PC, no damage can be caused by the cable.
If the systems are installed in impermissible installation locations, the approvals
complying to UL 508 and EN 60950 are annulled.
A Panel PC 670 with a DC power supply is considered an open operating
resource (power supply side). Therefore, the installation must fulfill the
requirements for fireproof housing.
1.9 Shielded Cable
Caution
When connecting periphery units, ensure that shielded cable and metallic
connectors are used, otherwise operation authorization is annulled! Fix the
interface cable plugs to the PC housing with the aid of a screwdriver. This
improves the electrical screening.
1.10 Touch Front
According to the manufacturer, the maximum permissible pressure which may
be applied to the touch screen is 25 gram using a plastic pen with a 1 mm
radius and 50 gram using a 1.6 cm thick silicone finger.