Construction
PB3 base unit comprising:
1 Base unit with 7 connection terminals
2 Switch assembly with 4 connection terminals for fan control.
The above is designed to snap into position.
Not shown: Temporary transparent cover (recyclable PET) to protect the
base unit and the connection terminals during the construction phase.
PBAS electronic assembly, comprising
3 Printed circuit board with rotary knob for setpoint adjustment
4 Unit cover
Mounting
Mounting instructions (Ref. 35642) are enclosed with the operating unit.
The room operating unit may be flush-mounted in a wall box or screwed
directly onto a wall.
When using the built-in temperature sensor, the following must be noted:
Mount in the occupied area, approximately 1.5 m above floor level and
at least 0.5 m from any adjacent wall
Do not expose to direct sunlight
Do not mount on external walls, in recesses, behind curtains or in the
vicinity of chimneys, doors and lamps.
See sheet 1659 for dimensions and further mounting instructions.
PBAS terminal layout
w
50939
1
2
3
4
5
6
7
L
I
II
III
1
2
3
4
PBAS
t
RA
PB
Room temperature sensor
Room temperature sensor (SGND)
Setpoint adjustment (SGND)
Setopint adjustment
Service bus (SGND)
Service bus (PB-Service)
Fan control switch
Service socket (FCC telephone socket)
for use with PRONTO IRC only
60156