13.1.2 Create plant messages
Start
1. In primary navigation, select "Administration".
2. Click the name of the desired plant.
3. In secondary navigation, select "Plant notifications".
4. Click "Add notification".
Basic data
You configure the notification in "Basic data".
Multiple recipients can be entered, with each e-mail address separated by a
comma.
"Send on" triggers a notification for incoming and/or outgoing alarms. A
notification is sent for both cases for setting "Both".
Click the message token directly to add it to the notification.
The bracket tokens [Appearing]…[/Appearing] and
[Disappearing]…[/Disappearing] are available based on "Send on". The
notification includes the text as defined by you between the brackets. Only the
applicable text is added to the notification for "Both".
Tip: To add a subject line, e.g. the [SiteName], copy it from the actual message
to the subject.
Alarm classes
Restrict the alarms sent via e-mail in "Alarm classes" (see "Alarm classes
[➙ 38]").
Alarm times and excluded dates
Under "Alarm times" and "Exception dates", define the times you want to
receive (or not receive) notifications.
For "Alarm times" and "Excluded dates", an active entry is only made after
clicking " "; clicking " " deletes the entry.