13 Appendix: Detail information
As a supplement to the main part, the appendix depicts information and workflows
that may be more or less relevant to the application.
13.1 Alarms
13.1.1 Alarm classes
Alarms classes are used to limit the type of alarms sent to you via e-mail. The
following alarm classes are currently available:
Alarm classes Type of alarms on…
OCI670, OZW672, internal
OCI670, OZW672, connected
controllers
Documentation e.g. C5712 LPB controller manuals
Class 0 ● Fault input (urgent)
● No bus power supply.
LPB fault priority >= 5
Class 1 Unused
Class 2 ● Fault input (not urgent)
● Faults gateway/web server
Unused
Class 3 Unused
Class 4 Connection supervision
Classes 5 to 15 Unused (Climatix POLxxx only)
● All alarm classes are selected by default
● Selected alarm classes, that are not used by your gateway/web server, are
simply ignored
This means the following for your application:
● Clearing alarm class 2 means that low-priority alarms are not sent via e-mail
● Clearing alarm class 4 means that no e-mail is sent when your plant goes
offline