Activate an alarm notification for a connection failure in excess of 5 minutes:
1. In the basic data, select "Connection supervision": On.
2. In secondary navigation, select the "Plant notifications" menu.
3. Click "Add alarm notification".
4. In addition to the text, it is the recipient e-mail address that is particularly
important under Basic settings.
5. Under Alarm classes, select "Alarm class 4" (Connection Supervision) only.
The tenant administrator can change the
default setting for connection
supervision. This takes place at "Administration > Tenants > 'my tenant' > Basic
data > Connection Supervision (default)"
9.1.3.1 Delete or hide plants
Delete plants
The plant is moved to the "Unassigned" tab. The user can no longer access the
plant. Only the tenant administration can reassign them or reactivate them using an
activation key. In contrast to "Hide" plant, settings specific to the plant are also
deleted.
Hide plants
In contrast to deleting a plant, the specific plant settings are retained under hide
plant and are immediately available on the plant is reassigned.
9.1.4 Plant operation
The plant operation menu is a link here to "Operating >'my plant' > Alarms".
Connection
Supervision