User Manual

68/90
Building Technologies M-bus System CE1P5361en
HVAC Products 8 Addendum 08.02.2007
8.3 Search run of central units OZW10 and
OZW111
The OZW10 and OZW111 identify connected M-bus devices with the help of their auto-
matic search run.
To match the search behavior of the central units to actual needs, they can be config-
ured with the help of ACS Service or ACS Operation using the "Applications – Popcard"
menu on page "Setup M-bus":
Type of addressing on the M-bus (the types of addressing of the M-bus are de-
scribed in subsection 5.4.2 "Fundamentals"):
Primary addressing: The search run only searches for primary-addressed devices.
The primary addresses of the M-bus device are between 1 and 250. Each device
must have a unique address. Not all devices have a primary address. Some de-
vices only have a secondary address
Secondary addressing: The search run only searches for secondary-addressed
devices. The secondary address space is nearly unlimited. When supplied, each
secondary-addressable device already has a unique secondary address. Depend-
ing on the type of device, the secondary address can be changed by changing the
customer number. Note: If a secondary-addressed device also has a primary ad-
dress (>0), it will then only be addressed with its primary address
Primary and secondary addressing: The search run searches for primary- and
secondary-addressed devices
Baud rates on the M-bus: Here, it is possible to select the Baud rates at which
the central unit searches for devices on the M-bus:
The OZW10 can search for devices at Baud rates of 300, 2,400 and 9,600. The
default setting is 300 and 2,400 Baud
The OZW111 can search for devices at Baud rates of 300 and 2,400. The default
setting is 300 and 2,400 Baud
Number of M-bus devices: This setting is only available with the OZW10 and de-
fines when the search run shall be aborted. The OZW10 starts the search run as
soon as this setting is changed. It stops the search run as soon as the respective
number of devices has been found. The number of M-bus devices also includes all
devices of the Siemeca™ AMR system that are connected to the M-bus via the
WTX16 or WTT16 radio nodes: Other radio nodes, MEGATRON
®
2, VOLUTRON
®
2,
WHE26 or AEW36.2.
Device search run: This setting is only available with the OZW111. This type of
central unit starts the search run when setting it to "On". All entries relating to the
devices previously found will be canceled. The search run is completed when the
value changes back to "Off"
Number of M-bus devices (actual): Here, the number of M-bus devices found is
displayed. Each of the 2 activated inputs of the AEW… is regarded as 1 device.