8.2.2 Sources
Phoenix Contact GmbH & Co.
Flachsmarktstrasse 8-28
D-32825 Blomberg
Tel. (052 35) 3-00
Fax (052 35) 3-4 12 00
E-Mail: info@phoenixcontact.com
Internet: www.phoenixcontact.com
Phoenix Contact AG
Ringstrasse 26
CH-8317 Tagelswangen
Tel. (052) 354 55 55
Fax (052) 354 56 99
E-Mail: phoenixcontact@bluewin.ch
Phoenix Contact GmbH
Favoritenstrasse 321
A-1108 Wien
Tel. (01) 68076
Fax (01) 6887620
E-Mail: info@phoenixcontact.at
Internet: www.phoenixcontact.at
8.2.3 Mounting notes
Protection against transients is mounted on DIN rails.
8.2.4 Regulations for installation
Full scale protection against transients is based on a 3-stage protection concept:
Gas-filled charge eliminator – ZNR – suppressor diode
The protective function is ensured only when the installation is correctly made!
In accordance with regulations, the DIN rail must be connected to the rail for po-
tential equalization in the building
For notes on installation of plant in compliance with EMC directives, refer to Data
Sheet N2034
The polarity of the protective components must be observed! The device to be
protected must always be connected to output “OUT” of the protective device that
guards against transients
12
3
4
IN
OUT
J1J2
21
4
3
IN
OUT
RxTx +
RxTx -
M-bus
12
3
4
IN
OUT
+
-
WSF...
12
3
4
IN
OUT
AEW21.2
WSD
1
2
34
IN
OUT
WSF...
M-bus
M-Bus
M-bus
RS-485
OZW10
WZC-P...
Type 1
Type 3
Type 1 Type 2
M-bus
RS-485
Type 3
RS-485
24
25
24
25
5361Z18