5 Engineering
5.1 Introduction
This chapter covers fundamentals of engineering.
Following is required for the M-bus system, depending on the application:
PC (refer to subsection 2.1.9 "Equipment combinations")
PC software (plant operating software ACS7…, recommended is ACS741 or
ACS785, depending on the application, refer to subsection 2.2.2 "Use")
2 modems or standard null modem cable (refer to section 6.1 "Communication
between ACS7… and OZW…")
M-bus central units OZW… (refer to sections 2.2 "M-bus central unit OZW10" and
2.3 "M-bus central unit OZW111")
M-bus repeater WZC-R250 (refer to section 2.6 "M-bus repeater WZC-R250")
M-bus signal converter WZC-P… (refer to sections 2.4 "M-bus signal converter
WZC-P250" and 2.5 "M-bus signal converter WZC-P60")
Components for lightning protection (refer to section 8.2 "Protection against tran-
sients ")
Cable (refer to sections 5.4 "M-bus" and 5.5 "RS-485 port")
5.2 PC software
The following general conditions apply to the ACS7… programs "ACS Operation",
"ACS Alarm", "ACS Batchjob" and "ACS Service":
In terms of programs, the number of plants is not limited. The number of supported
communication centers is only limited by the size of the PC’s hard disk
With ACS7… V3.0 or higher, the maximum number of COM ports is unlimited. With
the former versions, the maximum number of COM ports is 4
For every direct connection to a communication center, a COM port and a standard
null modem cable are required (refer to section 6.1 "Communication between
ACS7… and OZW…")
Several communication centers can be connected via COM port using a modem.
For the COM port and each communication center, one modem is required
2 different programs can be connected simultaneously to 2 different plants via dif-
ferent COM ports. Within one and the same program, it is not possible to have a
simultaneous connection to several plants
ACS Operation and ACS Batchjob can be connected simultaneously to the same
plant
5.3 Calculation of the required number of M-bus
central units
5.3.1 M-bus central unit OZW10
Internally, the OZW10 stores all device data required for the local display and the
memory card. Data storage is dynamic. This means that each M-bus device only uses
the amount of storage space it needs. With certain types of M-bus devices (e.g.
SONOGYR
®
energy, MEGATRON
®
2), the amount of data to be transmitted can be
parameterized. With the Siemeca™ AMR devices, the amount of data is determined by
the WTX16 or WTT16 radio node on the M-bus.
Using the ACS7…, the device data can be accessed via the internal storage of the
OZW10 or directly via the devices on the M-bus. Direct access to the devices is ac-