Data Sheet for Product

OpenAir
®
GPC Series, Spring Return, 35 lb-in, Rotary Electronic Damper Actuators Technical Instructions
Document Number 155-782
February 26, 2019
Siemens Industry, Inc. Page 5
Sizing
The type of actuator required depends on several factors:
1. Obtain damper torque ratings (lb-in/ft
2
or Nm/m
2
) from the damper manufacturer.
2. Determine the area of the damper.
3. Calculate the total torque required to move the damper:
Total Torque =
SF
AreaDamper Rating Torque
1
4. Select a spring return actuator using Table 1.
1
Safety Factor: When calculating the total torque required, a safety factor should
be included for unaccountable variables such as slight misalignments, aging of
the damper, and so on. A suggested safety factor is 0.80.
Table 2. Sizing.
Total Torque
Actuator
20 lb-in (2Nm)
GQD
> 20 lb-in < 35 lb-in (> 2 Nm < 4 Nm)
GPC
>35 lb-in 62 lb-in (>4 Nm 7 Nm)
GMA
>62 lb-in 160 lb-in (>7 Nm 18 Nm)
GCA
>160 lb-in 320 lb-in (>18 Nm 36 Nm)
Tandem GCA
ASK73.2U*: Tandem mounting bracket with any combination of GCA16x.
ASK73.1U*: Tandem mounting bracket for all other GCAx actuators.
*NOTE: Mechanically coupled actuators must be of the exact same type. Use the correct mounting bracket.
Mounting and
Installation
The shaft adapter can be mounted on either side of the actuator. The actuator
mounting orientation and shaft length determine how they will be mounted on the
actuator.
The minimum damper drive shaft length is 3/4-inch (20 mm).
See Specifications for the minimum and maximum damper shaft dimensions.
A mounting bracket is included with the actuator.
See the detailed installation instructions included with each actuator.
Auxiliary Switches
Switch
Switch
Makes
Switch
Breaks
A (fixed 5°)
< 5°
> 5°
B (fixed 85°)
> 85°
< 85°
NOTE: Both sets of contacts are open when actuator
is between 5° and 85°. Switches may be wired in a
Normally Closed or Normally Open position.
CAUTION:
Mixed switch operation to the switching outputs of
both dual end switches (5° and 85°) is not
permitted.
Either AC line voltage from the same phase must
be applied to all four outputs of the fixed dual end
switches, or UL-Class 2 voltage must be applied to
all four outputs.