Catalog
usa.siemens.com/hvac
Pneumatics
F-56
Medium
Switch ActionManual Reset
Ambient Temperature Range
Maximum Overpressure
Mounting Position
Body
Electrical Ratings
Conduit Opening
Sample Line Connectors
Material
Agency Approvals
Dimensions
Shipping Weight
Specifications
Product Ordering
Setpoint Range
(Field Adjustable)
Switching
Action/Reset Factory Setpoint Accuracy* Differential* Part No.
141-0518
141-0575
141-0574
Accessories & Service Kits F-83
Accessories Ordering
Description Part No.
269-062
189-142
Dimensions
(Figure 3)
ELECTRICAL CONNECTIONS
(
SEE FIGURE 3
)
Before pressure is applied to the diaphragm,
the switch contacts will be in the normally
closed (NC) position as shown in Figure 3.
The snap switch has screw top terminals
with cup washers. Wire alarm or control ap-
plication as shown in Figure 4.
(Figure 4)
(Figure 2)
SPECIFICATIONS
MODEL AFS-460 AIR
PRESSURE SENSING
SWITCH WITH MANUAL
RESET FEATURE
Mounting Position:
In order to meet lowest operating
specications, mount with the dia-
phragm in any vertical plane.
Set Point Range:
0.40 ± 0.06"w.c. to 12.0"w.c.
Field Adjustable
“Operate Range”:
0.46"w.c. to 12.0" w.c.
Measured Media:
Air
Maximum Pressure:
½ psi (0.03 bar)
Life:
Exceeds UL-recognized mechanical
endurance test of 6,000 cycles mini-
mum at 0.5 psi maximum pressure
each cycle and at maximum rated
electrical load
Electrical Rating @ 60 Hz.:
15A @ 125, 250, or 277 VAC.
½ A @ 125 VDC, ¼ A @ 250 VDC.
¼ hp @ 125 VAC; ½ hp @ 250 VDC.
Contact Arrangement:
SPST–NC (manual reset)
Electrical Connections:
8-32 screw-top terminals with cup
washers
Conduit Connection:
⅞" diameter opening accepts ½"
conduit
Sample Line Connectors:
Male, externally threaded
7
⁄
16
" 24 UNS
2A thread, complete with nut and self-
aligning ferrule
Sample Line Connections:
Connectors accept ¼" OD rigid or
semi-rigid tubing
Approval and Recognition:
UL, CSA, CE
Shipping Weight:
1.2 lbs.
Accessories:
• P/N 18311 Slip-on ¼" OD Tubing
Adapter, suitable for slipping on ex-
ible plastic tubing
• Sample line probes
• Orice plugs (pulsation dampers)
FIELD ADJUSTMENT
The adjustment range of an AFS-460 Air
Switch is 0.4" ± 0.06" w.c. to 12.0" w.c. To
adjust the set point, turn the adjusting screw
counterclockwise until motion has stopped.
Next, turn the adjusting screw four complete
turns in a clockwise direction to engage the
spring. From this point, the next ten turns will
be used for the actual calibration. Each full
turn represents approximately 1.16" w.c.
Please note: To properly calibrate an air
switch, a digital manometer or other mea-
suring device should be used to conrm the
actual set point.