Catalog
usa.siemens.com/hvac
Pneumatics
F-18
Control Action
Operating Range
Sensitivity Fixed
Temperature Response
Maximum Ambient Temperature
Dial Graduations
Normal Air Supply Pressure
Maximum Operating Pressure
Dimensions
Air Consumptionfor Compressor Sizing
Cover Style
Cover Finish
Shipping Weight
Specifications
Accessories & Service Kits F-83
Product Ordering
Description
Thermostat
Part No.
2
Cover
Assembly
832-0120 856-036
832-0490 856-046
1
832-0500 856-044
832-1260 856-044
Ordering Notes:
856-046,856-014,
856-055,
Thermostat
comes complete
with cover.
TECH TIP
1. Remove the cover.
2. Measure the ambient temperature.
3. Set the setpoint dial to the ambient temperature.
4. Measure the controller output pressure (branch pressure).
5. Turn the calibration screw(s) until the branch pressure equals the midpoint of the control span
[usually 8 psi (55 kPa)].
6. Reposition the cover.
DATE PAGE Descriptionofedits