SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate fault is output when the operating hours set here are reached.
Dependency: Refer to: p0650
Refer to: A01590
Note: For p0651 = 0, the operating hours counter is disabled.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
Description: Sets the command source.
Value: 0: No Macro
2: Terminals
100: EAQ1
101: EAQ2
110: Set enable signals
120: FBM (fault, operation, signal)
140: CDS
150: MOP 1
152: MOP 3
181: 2 Wire type 2
182: 2 Wire type 3
183: 3 Wire type 1
184: 3 Wire type 2
200: CAN Control
Caution: When executing a specific macro, the corresponding programmed settings are made and become active.
p0651[0...n] Motor operating hours maintenance interval / Mot t_op maint
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0 [h] 150000 [h] 0 [h]
p0700[0...n] Command source selection / Cmd src sel
CU230P-2 CAN Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
0 200 0