User Manual

List of Parameters
Parameters
1-81
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Defines the rated overtemperature of the stator winding referred to the ambient temperature.
Dependency: For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description: Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency: For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description: Displays the ambient temperature of the motor temperature model.
Description: Displays the stator core temperature of the motor temperature model.
Description: Displays the stator winding temperature of the motor temperature model.
p0627[0...n] Motor overtemperature, stator winding / Mot T_over stator
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: 21_2 Unit selection: p0505
Min Max Factory setting
20 [K] 200 [K] 80 [K]
p0628[0...n] Motor overtemperature rotor winding / Mot T_over rotor
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: 21_2 Unit selection: p0505
Min Max Factory setting
20 [K] 200 [K] 100 [K]
r0630[0...n] Motor temperature model ambient temperature / MotTMod T_amb.
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
- [°C] - [°C] - [°C]
r0631[0...n] Motor temperature model, stator core temperature / MotTMod T_core
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
- [°C] - [°C] - [°C]
r0632[0...n] Motor temperature model, stator winding temperature / MotTMod T_copper
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
- [°C] - [°C] - [°C]