SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the properties supported by the power unit hardware.
Description: The duty cycles can be overloaded provided that the drive converter is operated with its base load current before
and after the overload. This is based on a load duty cycle of 300 s.
Value: 0: Load duty cycle with high overload for vector drives
1: Load duty cycle with low overload for vector drives
Dependency: Refer to: r3996
Notice: The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note: When the parameter is changed, all of the motor parameters, the technological application and the control mode
are pre-assigned according to the selected application. The parameter has not influence when calculating the ther-
mal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
Description: The duty cycles can be overloaded provided that the drive converter is operated with its base load current before
and after the overload. This is based on a load duty cycle of 300 s.
Value: 0: Load duty cycle with high overload for vector drives
1: Load duty cycle with low overload for vector drives
Dependency: Refer to: r3996
Notice: The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note: When the parameter is changed, all of the motor parameters, the technological application and the control mode
are pre-assigned according to the selected application. The parameter has not influence when calculating the ther-
mal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
r0204[0...n] Power unit hardware properties / PU HW property
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: PDS
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 RFI filter available Yes No -
07 F3E regenerative feedback into the line sup-
ply
Yes No -
08 Internal Braking Module Yes No -
12 Safe Brake Control (SBC) supported No Yes -
14 Internal LC output filter Yes No -
p0205 Power unit application / PU application
PM230 Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1, 2) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 1
p0205 Power unit application / PU application
PM240
PM250, PM260
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1, 2) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0