SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Binector input for CANopen status word bit 8.
Dependency: Refer to: r8784
Description: Binector input for CANopen status word bit 14.
Dependency: Refer to: r8784
Description: Binector input for CANopen status word bit 15.
Dependency: Refer to: r8784
Description: Sets the automatic BICO interconnection of the CANopen control word.
Value: 0: No interconn
1: Interconnection
Dependency: Refer to: r2050, r2090, r2091, r2092, r2093, r8750, r8795
Note: The following BICO interconnections are automatically established if the CANopen control word is mapped at one
of the locations x = 0 ... 3 in the receive process data buffer.
BI: p0840.0 = r209x.0
BI: p0844.0 = r209x.1
BI: p0848.0 = r209x.2
BI: p0852.0 = r209x.3
BI: p2103.0 = r209x.7
The write access is rejected if a CANopen control word is not mapped at one of these locations.
This also causes the project download of the commissioning software to be canceled.
p8785 BI: CAN status word bit 8 / Status word bit 8
CU230P-2 CAN Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p8786 BI: CAN status word bit 14 / Status word bit 14
CU230P-2 CAN Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p8787 BI: CAN status word bit 15 / Status word bit 15
CU230P-2 CAN Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p8790 CAN control word - auto interconnection / STW interc auto
CU230P-2 CAN Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(3), T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0