Description: Selects the signal source for the direction of rotation during emergency operation (ESM).
0 = The direction of rotation of the setpoint parameterized for emergency operation is maintained.
1 = The direction of rotation of the setpoint parameterized for emergency operation is reversed.
Warning: The direction reversal is not taken into account if p3881 has a value of 4 (technology controller) and the technology
controller is also active as the setpoint source.
Description: Sets the signal source for the technology controller's setpoint in emergency operation (ESM).
Note: If p3884 = 0, the technology controller uses the setpoint from p2253.
Description: Indicates how often emergency operation (ESM) has been activated (index 0) and how many faults have occurred
during emergency operation (index 1).
Index: [0] = Number of activations of emergency operation
[1] = Number of faults during emergency operation
Description: Resets the number of activations of emergency operation and the number of faults which have occurred (in r3887).
0 = Do not reset
1 = Reset
p3883 BI: ESM direc. rot. / ESM direc. rot.
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p3884 CI: ESM setpoint technology controller / ESM setp tech_ctrl
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
r3887[0...1] ESM number of activations and faults / ESM num activ+flt
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
p3888 ESM reset number of activations and faults / ESM reset act flts
Access level: 4 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0