User Manual
Parameters
List of Parameters
1-322
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets a fixed value for torque.
Dependency: Refer to: p2900, p2901
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can, for example, be used to interconnect a supplementary torque.
Description: Sets the delay time for external fault 3.
Dependency: Refer to: p2108, p3111, p3112
Refer to: F07862
Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
Refer to: F07862
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
p2930[0...n] CO: Fixed value M [Nm] / Fixed value M [Nm]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2003 Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
-100000.00 [Nm] 100000.00 [Nm] 0.00 [Nm]
p3110 External fault 3, power-up delay / Ext fault 3 t_on
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
p3111[0...n] BI: External fault 3, enable / Ext fault 3 enab
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1
p3112[0...n] BI: External fault 3 enable negated / Ext flt 3 enab neg
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0