Description: Displays the status word of the technology controller.
Description: Sets the signal source to switch in/switch out the "staging" function.
1 signal: The function is switched in.
Value: 0: Motor staging disabled
1: Motor staging enabled
Note: The technology controller must be activated (p2200) and configured (p2251 = 0) in order to use the "staging" func-
tion.
Negative speed setpoints should be excluded.
r2349.0...12 CO/BO: Technology controller status word / Tec_ctrl status
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller de-activated Yes No -
01 Technology controller limited Yes No -
02 Technology controller, motorized potentiom-
eter limited max.
Yes No -
03 Technology controller, motorized potentiom-
eter limited min.
Yes No -
04 Technology controller speed setpoint total in
setpoint channel
Yes No -
05 Technology controller RFG bypassed in the
setpoint channel
Yes No -
06 Technology controller starting value at the
current limit
No Yes -
08 Technology controller actual value at the
minimum
Yes No -
09 Technology controller actual value at the
maximum
Yes No -
10 Technology controller output at the mini-
mum
Yes No -
11 Technology controller output at the maxi-
mum
Yes No -
12 Fault response active Yes No -
p2370[0...n] Staging enable / Staging enab
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 1 0