Parameters
List of Parameters
1-308
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the output signal of the technology controller.
Dependency: Refer to: p2295
Description: Sets the scaling for the output signal of the technology controller.
Description: Sets the signal source for the scaling value of the technology controller.
Dependency: Refer to: p2295
Description: Sets the signal source for the maximum limiting of the technology controller.
Dependency: Refer to: p2291
Note: In order that the output of the technology controller does not exceed the maximum speed limit, its upper limit p2297
should be connected to the actual maximum speed r1084.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
Description: Sets the signal source for the minimum limiting of the technology controller.
Dependency: Refer to: p2292
Note: If the technology controller is rotated in a negative direction in mode p2251 = 0, its lower limit p2298 should be con-
nected to the actual minimum speed r1087.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
r2294 CO: Technology controller output signal / Tec_ctrl outp_sig
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [%] - [%] - [%]
p2295 CO: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
-100.00 [%] 100.00 [%] 100.00 [%]
p2296[0...n] CI: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 2295[0]
p2297[0...n] CI: Technology controller maximum limit signal source / Tec_ctrl m_lm s_sc
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1084[0]
p2298[0...n] CI: Technology controller minimum limit signal source / Tec_ctrl min_l s_s
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 2292[0]