User Manual
Parameters
List of Parameters
1-278
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the code of the last alarm that occurred.
Note: 0: No alarm present.
Description: Displays additional information about the fault that occurred for float values.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2136
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays additional information about the active alarm for float values.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2125, r2145, r2146
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays the second status word of faults and alarms.
r2132 CO: Actual alarm code / Actual alarm code
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r2133[0...63] Fault value for float values / Fault val float
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r2134[0...63] Alarm value for float values / Alarm value float
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r2135.12...15 CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
12 Fault motor overtemperature Yes No -
13 Fault power unit thermal overload Yes No -
14 Alarm motor overtemperature Yes No -
15 Alarm power unit thermal overload Yes No -