SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the currently effective lower torque limit.
Note: The effective lower torque limit is reduced with respect to the selected lower torque limit p1521, if the current limit
p0640 is reduced or the rated magnetizing current of the induction motor p0320 is increased.
This may be the case for rotating measurements (see p1960).
The torque limit p1520 can be re-calculated using p0340 = 1, 3 or 5.
Description: Displays the torque limit to limit the speed controller output.
Index: [0] = Upper limit
[1] = Lower limit
Description: Displays the limit for the torque-generating current component using the stall calculation, the current limit of the
power unit as well as the parameterization in p0640.
Index: [0] = Upper limit
[1] = Lower limit
Description: Sets the signal source for the scaling of the upper torque limiting to limit the speed controller output without taking
into account the current and power limits.
Description: Sets the signal source for the scaling of the lower torque limiting to limit the speed controller output without taking
into account the current and power limits.
r1539 CO: Lower effective torque limit / M_max lower eff
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Data set: -
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r1547[0...1] CO: Torque limit for speed controller output / M_max outp n_ctrl
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Data set: -
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r1548[0...1] CO: Stall current limit torque-generating maximum / Isq_max stall
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Data set: -
Units group: 6_2 Unit selection: p0505
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1552[0...n] CI: Torque limit upper scaling without offset / M_max up w/o offs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1
p1554[0...n] CI: Torque limit lower scaling without offset / M_max low w/o offs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1