SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the control word of the speed controller.
Description: Displays the status word of the speed controller.
r1406.4...15 CO/BO: Control word speed controller / STW n_ctrl
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 Hold speed controller I component Yes No 6040
05 Set speed controller I component Yes No 6040
11 Droop enable Yes No 6030
12 Torque control active Yes No 6060
15 Set speed adaptation controller I compo-
nent
Yes No -
r1407.0...15 CO/BO: Status word speed controller / ZSW n_ctrl
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 U/f control active Yes No -
01 Encoderless operation active Yes No -
02 Torque control active Yes No 6030,
6060,
8010
03 Speed control active Yes No 6040
05 Speed controller I component frozen Yes No 6040
06 Speed controller I component set Yes No 6040
07 Torque limit reached Yes No 6060
08 Upper torque limit active Yes No 6060
09 Lower torque limit active Yes No 6060
10 Droop enabled Yes No 6030
11 Speed setpoint limited Yes No 6030
12 Ramp-function generator set Yes No -
13 Encoderless operation due to a fault Yes No -
15 Torque limit reached (without pre-control) Yes No 6060