List of Parameters
1-118
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
When downloading settings 10, 11, 12, the buffer memory mode is automatically deactivated (p0014 = 0).
Value: 0: Inactive
1: Start a parameter reset
10: Starts to download setting 10
11: Starts to download setting 11
12: Starts to download setting 12
100: Start a BICO interconnection reset
300: Only Siemens internal
Caution: When the buffer memory is active (see p0014), the actual parameters are backed up from RAM to ROM when a
parameter set is loaded (p0970 = 10, 11, 12).
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Peculiarities of communication via PROFIBUS DP:
- Communication with Class 1 masters (e.g. S7 controllers) is interrupted.
- Communication with Class 2 masters (e.g. STARTER) is retained.
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
The following generally applies:
One index of parameters p2100, p2101, p2118, p2119, p2126, p2127 is not reset, if a parameterized message is
precisely active in this index.
Description: Setting to save parameters in the non-volatile memory.
Value: 0: Inactive
1: Save drive object
10: Save in non-volatile memory as setting 10
11: Save in non-volatile memory as setting 11
12: Save in non-volatile memory as setting 12
Dependency: Refer to: p1960, r3996
Caution: If a memory card (optional) is inserted, the following applies:
The parameters are also saved on the card and therefore overwrite any existing data!
Caution: The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Notice: Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
p0970 Reset drive parameters / Drive par reset
Access level: 1 Calculated: - Data type: Unsigned16
Can be changed: C(1, 30) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 300 0
p0971 Save parameters / Save par
Access level: 1 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 12 0