User Manual
List of parameters
Parameters
1-87
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the operating hours for the corresponding motor.
The motor operating time counter continues to run when the pulses are enabled. When the pulse enable is with-
drawn, the counter is held and the value saved.
Dependency: Refer to: p0651
Refer to: A01590
Note: The operating hours counter in p0650 can only be reset to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
Description: Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate fault is output when the operating hours set here are reached.
Dependency: Refer to: p0650
Refer to: A01590
Note: For p0651 = 0, the operating hours counter is disabled.
When setting p0651 to 0, then p0650 is automatically set to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
Description: Displays the number of inputs and outputs
Index: [0] = Number of digital inputs
[1] = Number of digital outputs
[2] = Number of digital input/outputs bidirectional
[3] = Number of analog inputs
[4] = Number of analog outputs
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the simu-
lation mode (p0795.x = 1) to terminal mode (p0795.x = 0).
p0650[0...n] Actual motor operating hours / Mot t_oper act
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [h] 4294967295 [h] 0 [h]
p0651[0...n] Motor operating hours maintenance interval / Mot t_op maint
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [h] 150000 [h] 0 [h]
r0720[0...4] CU number of inputs and outputs / CU I/O count
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1510
Min Max Factory setting
- - -
r0721 CU digital inputs terminal actual value / CU DI actual value
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1510, 2020, 2030,
2031, 2100, 2120, 2130, 2131, 2132,
2133
Min Max Factory setting
- - -