User Manual

Overview of faults and alarms
Faults and alarms
3-653
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Acknowledging faults
The list of faults and alarms specifies how to acknowledge each fault after the
cause has been remedied.
Tabelle 3-3 Acknowledgement of faults
Acknowledg-
ment
Description
POWER ON The fault is acknowledged via a POWER ON (switch Control Unit off and on again).
Note:
If this action has not eliminated the fault cause, the fault is displayed again immediately
after power-up.
IMMEDIATELY Faults can be acknowledged as follows:
1 Acknowledge by setting parameter:
p3981 = 0 --> 1
2 Acknowledge via binector inputs:
p2103
p2104
p2105
BI: 1. Acknowledge faults
BI: 2. Acknowledge faults
BI: 3. Acknowledge faults
3 Acknowledge using PROFIBUS control signal:
STW1.7 = 0 --> 1 (edge)
Note:
These faults can also be acknowledged by a POWER ON operation.
If this action has not eliminated the fault cause, the fault will continue to be displayed
after acknowledgment.
Safety Integrated faults
The "Safe Torque Off" (STO) function must be deselected before these faults are
acknowledged.
PULSE INHIBIT The fault can only be acknowledged with a pulse inhibit (r0899.11 = 0).
The same possibilities are available for acknowledging as described under acknowledge
IMMEDIATELY.