Description: Sets the motor pole pair number.
p0314 = 1: 2-pole motor
p0314 = 2: 4-pole motor, etc.
Dependency: For p0314 = 0, the pole pair number is automatically calculated from the rated frequency (p0310) and the rated
speed (p0311) and displayed in r0313.
Notice: If p0314 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly.
For induction motors, the value need only be input if the rated data of a generator is entered therefore resulting in a
negative rated slip. In this case, the number of pole pairs in r0313 is too low by 1 and must be manually corrected.
Description: Sets the torque constant of the synchronous motor.
p0316 = 0: The torque constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque constant.
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: This parameter is not used for induction motors (p0300 = 1xx).
Description: Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The magnetizing current p0320 for induction motors is reset when quick commissioning is exited with p3900 > 0.
If, for induction motors, the magnetizing current p0320 is changed outside the commissioning phase (p0010 > 0),
then the magnetizing inductance p0360 is changed so that the EMF r0337 remains constant.
p0314[0...n] Motor pole pair number / Mot pole pair No.
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 0
p0316[0...n] Motor torque constant / Mot kT
PM230
PM240
PM250, PM260
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3), U, T Scaling: - Dyn. index: MDS, p0130
Units group: 28_1 Unit selection: p0100 Func. diagram: -
Min Max Factory setting
0.00 [Nm/A] 400.00 [Nm/A] 0.00 [Nm/A]
p0320[0...n] Motor rated magnetizing current/short-circuit current / Mot I_mag_rated
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 5722
Min Max Factory setting
0.000 [Arms] 5000.000 [Arms] 0.000 [Arms]