Value: 0: IEC-Motor (50 Hz, SI units)
1: NEMA motor (60 Hz, US units)
2: NEMA motor (60 Hz, SI units)
Dependency: If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0337, p1800
Note: The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
Description: Identification of the Control Unit using an LED.
Note: While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
Description: Configuration of the motor when commissioning the motor.
Dependency: For standard induction motors (p0301 > 10000), bit 0 is automatically preassigned the connection type of the
selected data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
Refer to: p0304, p0305, p1082
Note: Re bit 0:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically con-
verted to the selected connection type (star or delta connection).
Re bit 1:
Operation with 87 Hz is only possible in the delta connection type. When selected, the maximum speed p1082 is
automatically preassigned for a maximum output frequency of 87 Hz.
Description: Sets the number of Command Data Sets (CDS).
Dependency: Refer to: p0010, r3996
Notice: When the data sets are created, short-term communication interruptions may occur.
Note: It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0124[0...n] CU detection via LED / CU detection LED
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: U, T Scaling: - Dyn. index: PDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p0133[0...n] Motor configuration / Motor config
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor connection type Delta Star -
01 Motor 87 Hz operation Yes No -
p0170 Number of Command Data Sets (CDS) / CDS count
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: C(15) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8560
Min Max Factory setting
2 4 2