User Manual

List of parameters
Parameters
1-41
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the measured actual value of the DC link voltage.
Dependency: Refer to: r0026
Notice: When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM240) a valid measured value is not sup-
plied. In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the dis-
play parameter.
Note: The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
Description: Displays the maximum output voltage.
Dependency: The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note: As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link volt-
age.
Description: Displays the actual output voltage of the power unit.
Dependency: Refer to: r0025
Note: The output voltage is available smoothed (r0025) and unsmoothed (r0072).
Description: Displays the maximum modulation depth.
Dependency: Refer to: p1803
r0070 CO: Actual DC link voltage / Vdc act val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_2 Unit selection: p0505 Func. diagram: 6723, 6724, 6730,
6731, 6799
Min Max Factory setting
- [V] - [V] - [V]
r0071 Maximum output voltage / U_output max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 1710, 6300, 6640,
6722, 6723, 6724, 6725, 6727
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0072 CO: Output voltage / U_output
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 1630, 6730, 6731,
6799
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0073 Maximum modulation depth / Modulat_depth max
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6723, 6724
Min Max Factory setting
- [%] - [%] - [%]