User Manual

List of parameters
Parameters
1-391
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the time constant for the differentiation (D component) of the free technology controller 2.
Note: Value = 0: Differentiation is de-activated.
Description: Sets the proportional gain (P component) of the free technology controller 2.
Note: Value = 0: The proportional gain is de-activated.
Description: Sets the integral time (I component, integrating time constant) of the free technology controller 2.
Note: Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
Description: Sets the maximum limit of the free technology controller 2.
Dependency: Refer to: p11292
Note: The maximum limit must always be greater than the minimum limit (p11291 > p11292).
Description: Sets the minimum limit of the free technology controller 2.
Dependency: Refer to: p11291
Note: The maximum limit must always be greater than the minimum limit (p11291 > p11292).
p11274 Free tec_ctrl 2 differentiation time constant / Ftec2 D comp T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p11280 Free tec_ctrl 2 proportional gain / Ftec2 Kp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 1000.000 1.000
p11285 Free tec_ctrl 2 integral time / Ftec2 Tn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 10000.000 [s] 30.000 [s]
p11291 CO: Free tec_ctrl 2 limit maximum / Ftec2 lim max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p11292 CO: Free tec_ctrl 2 limit minimum / Ftec2 lim min
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]