User Manual
Parameters
List of parameters
1-368
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
20507 hex: CU250D-2 PN V4.5
20508 hex: CU250D-2 PN V4.6
Description: Sets the profile for Ethernet/IP.
Value: 0: SINAMICS
1: ODVA AC/DC
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
ODVA: Open DeviceNet Vendor Association
Description: Sets the STOP mode for the Ethernet/IP ODVA profile (p8980 = 1).
Value: 0: OFF1
1: OFF2
Dependency: Refer to: p8980
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the scaling for the speed for Ethernet/IP ODVA profile (p8980 = 1).
Value: 123: 32
124: 16
125: 8
126: 4
127: 2
128: 1
129: 0.5
130: 0.25
131: 0.125
132: 0.0625
133: 0.03125
Dependency: Refer to: p8980
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p8980 Ethernet/IPprofile / Eth/IP profile
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p8981 Ethernet/IP ODVA STOP mode / Eth/IP ODVA STOP
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p8982 Ethernet/IP ODVA speed scaling / Eth/IP ODVA n scal
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
123 133 128